AERCO ProtoNode Gateway
User Manual
OMM-0080_0H AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 91 of 126
GF-129 Ph.: 800-526-0288 11/06/2014
Appendix C.6: Twelve C-Mores, Six ECS/SmartPlate, Four Modulex and Two ACS/BMS II
Table C-6: Twelve C-Mores, Six ECS/SmartPlate, Four Modulex and Two ACS/BMS II
Equip Point Name Name
Read
Only
BACnet
Type:ID
N2
Type
N2
ID
Lon SNVT
NAME
Lon SNVT
Lon
Direction
ModBus/
Unit
Address
Mlx Addr 1
1
01-Act Mod Lev boilerstate_1
AV:121
data
float
121 nvoMlxState1 inc count (9) Output (non-polled) 41009/1
1
02-Target Setpoint effectsetpt_1
AV:122
data
float
122 nvoMlxSetpt1 inc count (9) Output (non-polled) 41019/1
1
03-Req Outlet
Temp
setpt_1 AV:123
data
float
123 nviMlxSetptRq1 inc count (9) Input (non-polling) 41005/1
1
04-Net Direct Drive boilercmd_1 AV:124
data
float
124 nviMlxCmd1 inc count (9) Input (non-polling) 40002/1
1
05-Mod Lev In boilerload_1
AV:125
data
float
125 nvoMlxLoad1 inc count (9) Output (non-polled) 41201/1
1
06-Flow Sens
Temp
localsuptemp_1
AV:126
data
float
126 nvoMlxSupTmp1 inc count (9) Output (non-polled) 41003/1
1
07-Display Code dispcode_1
AV:127
data
float
127 nvoMlxDispCode1 inc count (9) Output (non-polled) 30001/1
1
11-Error Code errcode_1
AV:128
data
float
128 nvoMlxErrCode1 51 Output (non-polled) 40001/1
1
08-Unit Status unitstat_1
AV:129
data
float
129 nvoMlxStat1 inc count (9) Output (non-polled) 30002/1
1
09-Ret Flow Temp returntemp_1
AV:130
data
float
130 nvoMlxRetTmp1 inc count (9) Output (non-polled) 41004/1
Mlx Addr 2
2
01-Act Mod Lev boilerstate_2
AV:131
data
float
131 nvoMlxState2 inc count (9) Output (non-polled) 41009/
2
02-Target Setpoint effectsetpt_2
AV:132
data
float
132 nvoMlxSetpt2 inc count (9) Output (non-polled) 41019/2
2
03-Req Outlet
Temp
setpt_2 AV:133
data
float
133 nviMlxSetptRq2 inc count (9) Input (non-polling) 41005/2
2
04-Net Direct Drive boilercmd_2 AV:134
data
float
134 nviMlxCmd2 inc count (9) Input (non-polling) 40002/2
2
05-Mod Lev In boilerload_2
AV:135
data
float
135 nvoMlxLoad2 inc count (9) Output (non-polled) 41201/2