Aerco ProtoNode Gateway Rev 3 (with external LEDs) Uživatelský manuál Strana 47

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 126
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 46
AERCO ProtoNode Gateway
User Manual
OMM-0080_0H AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 47 of 126
GF-129 Ph.: 800-526-0288 11/06/2014
Appendix A: REFERENCE
Appendix A.1: Specifications
Appendix A.1: Specifications
ProtoNode RER
ProtoNode LER
Electrical
Connections
One 6-pin Phoenix connector, one RS-485
+/- ground port, power +/- frame ground
port.
One 3-pin RS-485 Phoenix connector, one
RS-485 +/- ground port.
One Ethernet-10/100 Ethernet port.
One 6-pin Phoenix connector, one RS-485
+/- ground port, power +/- frame ground
port.
One Ethernet 10/100 BaseT port.
One FTT-10 LonWorks port.
Approvals:
CE (EN55022;EN55024; EN60950), UL916, FCC Class A Part 15, DNP3 Conformance Tested,
OPC Self-tested for Compliance, RoHS Compliant, CSA 205 Approved
BTL Marked
LonMark Certified
Power
Requirements
Multi-mode power adapter: 9-30 VDC, 12-24 VAC
Physical
Dimensions
11.5 cm L x 8.3 cm W x 4.1 cm H (4.5 x 3.2 x 1.6 in.)
Weight:
0.2 kg (0.4 lbs)
Operating
Temperature:
-40°C to 75°C (-40°F to167°F)
Surge
Suppression
EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Humidity:
5 - 90% RH (non-condensing)
(Specifications subject to change without notice)
Appendix A.2: Compliance with UL Regulations
For UL compliance, the following instructions must be met when operating the ProtoNode.
The units shall be powered by listed LPS or Class 2 power supply suited to the expected operating
temperature range.
The interconnecting power connector and power cable shall:
o Comply with local electrical code.
o Be suited to the expected operating temperature range.
o Meet the current and voltage rating for the ProtoNode/Net
Furthermore, the interconnecting power cable shall:
o not exceed 3.05m (118.3”) in length.
o Be constructed of materials rated VW-1 or FT-1 or better.
If the unit is to be installed in an operating environment with a temperature above 65 °C, it should
be installed in a Restricted Access Area requiring a key or a special tool to gain access
This device must not be connected to a LAN segment with outdoor wiring.