Aerco ProtoNode Gateway Rev 3 (with external LEDs) Uživatelský manuál Strana 109

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 126
  • Tabulka s obsahem
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 108
AERCO ProtoNode Gateway
User Manual
OMM-0080_0H AERCO International, Inc. 100 Oritani Dr. Blauvelt, NY 10913 Page 109 of 126
GF-129 Ph.: 800-526-0288 11/06/2014
Table C-7: Eight C-More Boilers/Heaters and BST/WHM Master
Equip Point Name Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon SNVT
NAME
Lon
SNVT
Lon Direction
ModBus
Address
4
Air Temp SMD_BAS_IP_HTR_04_[7] AV:607 Data Float 113
nvoHTR_04_8
inc count (9) Output (non-polled) 30607
4
Flame Strength SMD_BAS_IP_HTR_04_[8] AV:608 Data Float 114
nvoHTR_04_9
inc count (9) Output (non-polled) 30608
4
Fire Rate In SMD_BAS_IP_HTR_04_[9] AV:609 Data Float 115
nvoHTR_04_10
inc count (9) Output (non-polled) 30609
4
Fire Rate Out SMD_BAS_IP_HTR_04_[10] AV:610 Data Float 116
nvoHTR_04_11
inc count (9) Output (non-polled) 30610
4
Unit Type SMD_BAS_IP_HTR_04_[11]
AV:611 Data Float 117
nvoHTR_04_12
inc count (9) Output (non-polled) 30611
4
Unit Size SMD_BAS_IP_HTR_04_[12]
AV:612 Data Float 118
nvoHTR_04_13
inc count (9) Output (non-polled) 30612
4
Value State SMD_BAS_IP_HTR_04_[13] AV:613 Data Float 119
nvoHTR_04_14
inc count (9) Output (non-polled) 30613
4
Net Remote Setpt SMD_BAS_IP_HTR_04_[14] AV:614 Data Float 120
nvoHTR_04_15
inc count (9) Output (non-polled) 30614
4
Run Cycles Upper SMD_BAS_IP_HTR_04_[15] AV:615 Data Float 121
nvoHTR_04_16
inc count (9) Output (non-polled) 30615
4
Run Cycles Lower SMD_BAS_IP_HTR_04_[16] AV:616 Data Float 122
nvoHTR_04_17
inc count (9) Output (non-polled) 30616
4
Run Hours Upper SMD_BAS_IP_HTR_04_[17]
AV:617 Data Float 123
nvoHTR_04_18
inc count (9) Output (non-polled) 30617
4
Run Hours Lower SMD_BAS_IP_HTR_04_[18]
AV:618 Data Float 124
nvoHTR_04_19
inc count (9) Output (non-polled) 30618
4
Oxygen Level SMD_BAS_IP_HTR_04_[19] AV:619 Data Float 125
nvoHTR_04_20
inc count (9) Output (non-polled) 30619
Blr Addr 5
5
Comm Address SMD_BAS_IP_HTR_05_[0] AV:700 Data Float 126
nvoHTR_05_1
inc count (9) Output (non-polled) 30700
5
Unit Status SMD_BAS_IP_HTR_05_[1] AV:701 Data Float 127
nvoHTR_05_2
inc count (9) Output (non-polled) 30701
5
Fault Code SMD_BAS_IP_HTR_05_[2]
AV:702 Data Float 128
nvoHTR_05_3
inc count (9) Output (non-polled) 30702
5
Outlet Temp SMD_BAS_IP_HTR_05_[3]
AV:703 Data Float 129
nvoHTR_05_4
inc count (9) Output (non-polled) 30703
5
FFWD Temp SMD_BAS_IP_HTR_05_[4] AV:704 Data Float 130
nvoHTR_05_5
inc count (9) Output (non-polled) 30704
5
Inlet Temp SMD_BAS_IP_HTR_05_[5] AV:705 Data Float 131
nvoHTR_05_6
inc count (9) Output (non-polled) 30705
5
Exhaust Temp SMD_BAS_IP_HTR_05_[6] AV:706 Data Float 132
nvoHTR_05_7
inc count (9) Output (non-polled) 30706
5
Air Temp SMD_BAS_IP_HTR_05_[7] AV:707 Data Float 133
nvoHTR_05_8
inc count (9) Output (non-polled) 30707
5
Flame Strength SMD_BAS_IP_HTR_05_[8]
AV:708 Data Float 134
nvoHTR_05_9
inc count (9) Output (non-polled) 30708
5
Fire Rate In SMD_BAS_IP_HTR_05_[9]
AV:709 Data Float 135
nvoHTR_05_10
inc count (9) Output (non-polled) 30709
5
Fire Rate Out SMD_BAS_IP_HTR_05_[10] AV:710 Data Float 136
nvoHTR_05_11
inc count (9) Output (non-polled) 30710
Zobrazit stránku 108