AERCO ProtoNode Gateway
User Manual
Page 88 of 126 AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 OMM-0080_0H
11/06/2014 Ph.: 800-526-0288 GF-129
Table C-4: Four Modulex and One ACS/BMS II
Equip Point Name Name
Lon SNVT Lon Direction
4
05-Mod Lev In boilerload_4
AV:43
data
float
179 nvoMlxLoad4 inc count (9) Output (non-polled) 41201/4
4
06-Flow Sens
Temp
localsuptemp_4
AV:44
data
float
180 nvoMlxSupTmp4 inc count (9) Output (non-polled) 41003/4
4
07-Display Code dispcode_4
AV:45
data
float
181 nvoMlxDispCode4 inc count (9) Output (non-polled) 30001/4
4
11-Error Code errcode_4
AV:10
data
float
182 nvoMlxErrCode4 51 Output (non-polled) 40001/4
4
08-Unit Status unitstat_4
AV:46
data
float
183 nvoMlxStat4 inc count (9) Output (non-polled) 30002/4
4
09-Ret Flow Temp returntemp_4
AV:11
184 nvoMlxRetTmp4 inc count (9) Output (non-polled) 41004/4